Sări la conținut
Înapoi la căutare
Acest licitație a fost retrasă.

Germania – Servicii de inspecţie şi testare tehnică – Überprüfung ortsveränderlicher elektrischer Betriebsmittel an Potsdamer Schulen und Einrichtungen

Landeshauptstadt PotsdamGermaniaPublicat pe 03 aug. 2026
Deadline trecut

Descriere

1. General

The capital city of Potsdam intends to conclude a contract for the inspection of portable electrical equipment according to DGUV V4 for 27 educational institutions of the municipal school authority. If the offered service does not meet the specified technical requirements of the tender, the bidder must prove to the contracting authority (AG) with suitable means in his offer that the solution proposed by the bidder meets these technical requirements to the same extent.

2. Quantity

Inspection of portable electrical equipment in 27 educational institutions. The quantity of portable devices to be tested is estimated at approximately 35,000 devices per year. The aforementioned quantities of portable devices to be tested are estimates of the contracting authority. These are based on the experience of previous years and serve additionally as a guide for the contractor (AN).

3. Offer price and remuneration

The offered unit price is a fixed price that applies for the entire duration of the contract. The remuneration is made according to the number of devices proven and actually tested once a year.

4. Scope of services

a) Content of the inspection

Inspection of all portable electrical equipment available at the time of inspection, including connecting cables and connections of all protection classes in 27 schools/institutions (see Annex 1 to the tender - Overview of Schools). The scope of the inspection according to DIN EN 50678 and DIN EN 50699 (or equivalent) includes:

Visual inspection with the following contents:

- Damage to housings

- Defects in connecting cables

- Defects in the bending protection or strain relief of the connecting cables

- Signs of overload, misuse or unauthorized interference and modifications

- Proper condition of covers

- Safety-impairing contamination and corrosion

- Presence and condition of required air filters and cooling openings

- Unimpaired legibility of safety-related markings

Measurement process with the following contents:

- Testing of the resistance or continuity of the protective conductors

- Proof of insulation resistance (according to the protection class with closed switches)

- Measuring the leakage current

- Measuring the protective conductor or differential current and the touch current

- Checking the limit values for protective extra-low voltage

Carrying out and documenting a functional test:

- Attaching an "E-Check" inspection sticker with the date of the next inspection (date of the repeat inspection). Inspection intervals according to risk assessment in accordance with GUV-I 8524

- Preparation of an inspection report and logging of the individual measurement results

- Carrying out minor repairs to cables and plugs: pressing on cable ferrules, retightening strain reliefs, changing Schuko plugs and/or couplings. The material for this must be provided and calculated by the contractor

- Logging and segregating electrical equipment with technical defects

Stickers are to be provided by the contractor and permanently attached to the equipment. The costs for the stickers are to be included in the offer price. For equipment to which the inspection sticker cannot be sensibly attached, the contractor must choose a suitable marking (e.g. cable marker, cable tie with label field, etc.). Equipment that has failed the test must be marked with a large red sticker (lockout sticker) on the plug to indicate that this equipment is no longer safe to operate. The red stickers are to be provided by the contractor and included in the offer price accordingly. The defective equipment is to be handed over to the caretaker. The contracting authority is to be provided with a test protocol incl. defect list 1x per year digitally, which is to be attached as an annex to the invoice. The contracting authority decides on the further procedure for the defective equipment (repair, disposal, etc.). Repairs not listed above and disposal are not part of the contract. Further description of the scope of services (implementation period and inspection interval as well as inspection personnel to be used) under "Description of the Procurement".

Coduri CPV

Technical inspection and testing servicesTechnical inspection services

Documente și transmitere

Rezumat AI
Conectează-te pentru un rezumat AI

Contains data from Tenders Electronic Daily (TED), © European Union, ted.europa.eu — CC BY 4.0.

Achiziții similare